Breaker Size Calculator
Find the right circuit breaker size for your load. Accounts for the NEC 125% continuous load rule and gives you the next standard breaker size.
Calculate Breaker Size
Result
—
Calculated Current
—
Minimum Breaker
—
Recommended Standard
Formula
Current (A) = Watts ÷ Voltage
If continuous load: Minimum Breaker = Current × 1.25
Round up to the next standard breaker size
If continuous load: Minimum Breaker = Current × 1.25
Round up to the next standard breaker size
Standard breaker sizes: 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200A
Example Calculation
Sizing a breaker for a 3,000W electric water heater at 240V (continuous load):
Current = 3000W ÷ 240V = 12.5A
Continuous load: 12.5A × 1.25 = 15.6A minimum
Next standard breaker size = 20A
Continuous load: 12.5A × 1.25 = 15.6A minimum
Next standard breaker size = 20A
A 20A double-pole breaker at 240V is the correct choice for this water heater.
Practical Notes
- A continuous load is any load that runs for 3 or more hours without interruption.
- The NEC 125% rule means your load should not exceed 80% of the breaker rating continuously.
- Always size the wire to match or exceed the breaker — not just the load.
- For 240V loads, you need a double-pole breaker (two slots in your panel).
- This calculator provides guidance only. Have a licensed electrician verify sizing before installation.
Frequently Asked Questions
What size breaker do I need for a 1500W heater?
At 120V: 1500W ÷ 120V = 12.5A. Since it runs continuously, multiply by 1.25 = 15.6A. You need a 20A breaker — the next standard size above 15.6A. Do not use a 15A breaker for a continuous 12.5A load.
What is the 125% rule for circuit breakers?
The NEC requires continuous loads to not exceed 80% of the breaker's rating. Equivalently, size the breaker at 125% of the load current. Example: a 16A continuous load needs a 20A breaker (16A × 1.25 = 20A minimum rating).
What are standard circuit breaker sizes?
Common residential and commercial breaker sizes: 15A, 20A, 25A, 30A, 35A, 40A, 50A, 60A, 70A, 80A, 90A, 100A, 125A, 150A, 175A, 200A. You always round up to the next available size above your minimum requirement.