Wire Size Calculator

Find the right AWG wire size for your circuit based on current, run length, voltage, and maximum allowed voltage drop.

Calculate Wire Size (AWG)

Result

Recommended Wire Size
Ampacity (copper, 60°C)
Actual Voltage Drop

AWG Quick Reference (Copper, 60°C)

AWG Ampacity (A) Typical Use
AWG 14 15A Lighting, 15A circuits
AWG 12 20A General outlets, 20A circuits
AWG 10 30A Dryers, water heaters, 30A circuits
AWG 8 40A Ranges, AC units, 40A circuits
AWG 6 55A Large AC, 50A circuits
AWG 4 70A Sub-panels, large appliances
AWG 2 95A Large sub-panels
AWG 1/0 125A Service entrances
AWG 2/0 145A 200A service
AWG 4/0 195A Large commercial service

Example Calculation

Finding wire size for a 20A circuit with a 75ft one-way run at 120V, max 3% voltage drop:

Max allowed voltage drop = 120V × 3% = 3.6V
Try AWG 12 (1.98 Ω/1000ft): R = (1.98 ÷ 1000) × 2 × 75 = 0.297Ω
Voltage drop = 20A × 0.297 = 5.94V (4.95%) — too high
Try AWG 10 (1.24 Ω/1000ft): R = (1.24 ÷ 1000) × 2 × 75 = 0.186Ω
Voltage drop = 20A × 0.186 = 3.72V (3.1%) — marginal
Try AWG 8 (0.778 Ω/1000ft): R = (0.778 ÷ 1000) × 2 × 75 = 0.117Ω
Voltage drop = 20A × 0.117 = 2.34V (1.95%) — good

For a 20A, 75ft run at 120V with max 3%, AWG 8 is recommended.

Frequently Asked Questions

What wire size do I need for a 30 amp circuit?
For a standard 30A circuit, AWG 10 copper wire is the NEC minimum. For runs longer than 50 feet, consider AWG 8 to keep voltage drop under 3% at full load.
What is the 80% rule for wire sizing?
Wires should not carry more than 80% of their rated ampacity on a continuous basis (3+ hours). A 20A breaker circuit should carry no more than 16A continuously. This is built into NEC breaker sizing requirements.
Does wire length affect what size I need?
Yes. Longer runs increase resistance and cause more voltage drop. For runs over 50 feet, you often need to go up one gauge size (e.g., from AWG 12 to AWG 10) to stay within the 3% voltage drop recommendation.