Voltage Drop Calculator – Copper Wire
Copper is the default conductor for most fixed wiring — lower resistivity than aluminum means less drop for the same cross-section. Use this calculator to check whether your cable run meets the 3–5% voltage drop limit required by NEC, IEC 60364, and AS/NZS 3000. Covers single phase and three phase circuits in mm².
This calculator provides estimates only. Always verify against local wiring regulations and consult a qualified electrician.
Calculate Voltage Drop (Copper)
Voltage Drop Results
—
Voltage Drop (V)
—
Drop (%)
—
Voltage at Load (V)
—
Status
Formulas
Single phase copper:
VD (V) = 2 × L × I × R_per_metre
VD% = VD ÷ V × 100
VD% = VD ÷ V × 100
Three phase copper:
VD (V) = √3 × L × I × R_per_metre
Copper resistivity ≈ 1.72 × 10⁻⁸ Ω·m (at 20°C). Resistance increases with temperature — at 75°C operating temperature, multiply by approximately 1.25.
Copper Wire Resistance Reference
| Wire Size (mm²) | Resistance (mΩ/m) | Ampacity (A) |
|---|---|---|
| 1.5 mm² | 12.1 | 16 A |
| 2.5 mm² | 7.41 | 25 A |
| 4 mm² | 4.61 | 32 A |
| 6 mm² | 3.08 | 41 A |
| 10 mm² | 1.83 | 57 A |
| 16 mm² | 1.15 | 76 A |
| 25 mm² | 0.727 | 101 A |
| 35 mm² | 0.524 | 125 A |
Frequently Asked Questions
What is the voltage drop formula for copper wire?
Single phase: VD = 2 × L × I × R (factor of 2 for return conductor). Three phase: VD = √3 × L × I × R. Where R is resistance per metre in Ω/m. For 2.5mm² copper at 25A over 40 metres single phase: VD = 2 × 40 × 25 × 0.00741 = 14.82V. At 230V: 14.82 ÷ 230 × 100 = 6.4% — too high, upgrade to 4mm² or 6mm².
Why is copper preferred over aluminium for wiring?
Copper resistivity is about 1.72 μΩ·cm vs aluminium at 2.82 μΩ·cm — copper conducts 64% better per unit cross-section. A 2.5mm² copper cable has the same resistance as a 4mm² aluminium cable. Copper is also easier to terminate (aluminium requires anti-oxidant compound and special lugs to prevent connection failure from oxide layer formation).
What is the maximum acceptable voltage drop for copper wiring?
IEC 60364 recommends maximum 4% for most circuits, 3% for lighting. NEC suggests 3% for branch circuits and 5% cumulative (feeder + branch). For sensitive equipment (computers, medical devices, variable speed drives), keep drop under 2%. Higher voltage drop causes equipment to draw more current to compensate, generating heat and potentially shortening equipment life.